1.22
A commercial building with an electrical power sysytem that includes a significant number of 120-vac and 208-vac three-phase loads (four wire, WYE-connected). Computed, total load of 645 amps.
What size THHN aluminum conductor is required for the service when they are paralleled six times per phase?
a. #2, b. #1, c. #1/0, d. #2/0
Kaplan Answer = b. #1
According to NEC - 310.4 - Paralleled conductors shall be #1/0 and larger. There are a couple of exceptions, but they would not apply to this situation.
Am I missing something here or is this a Kaplan error? I couldn't find any errata information on their website.
Thanks and good luck to all on Friday!!